How to Pass Your Emergency Exit Light Audit

Emergency exit lighting compliance in Australia is one of those obligations that rarely demands attention until it fails under pressure. The alarm goes off, mains power cuts, and the corridor fills with smoke. Every occupant is now relying on the equipment your team last checked at an audit. That is either a reassuring thought or a concerning one, depending on how rigorously your team maintains the system.
In Australia, AS/NZS 2293 governs emergency escape luminaires and exit signs. The National Construction Code references it directly, and state fire authorities enforce it. It is not a guideline. It is a legal requirement for most commercial, industrial, and public buildings, and non-compliance carries real penalties. More importantly, it carries real risk.
This is what the standard requires, where facilities most often fall short, and what audit-ready compliance looks like in practice.

What Australian Standard 2293 Covers
AS/NZS 2293 covers three distinct parts. Part 1 covers design, installation, and commissioning. Routine service and maintenance obligations fall under Part 2. Part 3 sets the performance requirements for luminaires and exit signs.
Most facility managers are reasonably across Part 1 when a building is first fitted out. The gaps tend to appear in Part 2, which is the ongoing obligation that never goes away.
The standard applies to two distinct systems that must work together:
- Emergency escape luminaires: These illuminate floor-level pathways when mains power fails, providing safe movement through corridors, stairwells, and egress routes.
- Exit signs: These mark the exits themselves, using the running-man symbol under AS/NZS 2293.3, and must be visible from a defined viewing distance printed directly on the sign face.
Both systems must perform for a minimum of 90 minutes after mains power failure. That 90-minute floor-level light level must reach at least 0.2 lux (average 0.5 lux) in general areas, and at least 1 lux in stairwells.
Checkpoint Group's range of exit and emergency lighting covers the full spread of mounting configurations, including wall mount, ceiling mount, recessed blade, weatherproof, and twin-spot options, so you will find a compliant fitting for every building type and application.
The NCC's Part E4 on visibility, exit signs and warning systems sets out precisely how an emergency lighting system must operate to minimise risk during an evacuation, and makes compliance with AS/NZS 2293.1 a legal requirement for every required emergency lighting system in Australia.
The Testing Schedule Most Facilities Get Wrong
The maintenance requirements under AS/NZS 2293 Part 2 are specific, and they are where most facilities accumulate compliance risk over time. The schedule is not annual. It runs at monthly, six-monthly, annual, and ten-yearly intervals, each with distinct obligations.
Here is what each tier requires:
Monthly: A visual inspection confirming all luminaires and exit signs work correctly, show no damage, and have no obstructions. This is a quick check, but your team must complete and record it every month.
Six-monthly: A full 90-minute discharge test of every emergency and exit light on the premises, carried out by a competent person and logged in the maintenance register. This is the test most facilities either skip, defer, or perform incorrectly. The discharge must run for the full 90 minutes to confirm battery capacity under load.
Annual: A full inspection building on the six-monthly test, including review of mounting positions, viewing distances, egress path coverage, and a check of all documentation.
Ten-yearly: A comprehensive assessment of the entire system, including battery replacement where required and a full performance review against the current version of the standard.
Keep records on-premises in a logbook, paper or digital, for a minimum of seven years. When an auditor or building inspector arrives, those records need to be available immediately. Saying "we had it tested last year" without documentation to back it up does not constitute compliance.

What Gets Missed in Audits
Emergency lighting failures in compliance audits tend to cluster around the same issues. They are not usually the result of broken equipment. They trace back to maintenance that drifted, documentation that nobody kept, or installations that were never quite right from the start.
SafeWork NSW is direct on the point: every PCBU must ensure lighting enables safe evacuation in an emergency. The regulator also requires a competent person to test and maintain emergency lighting on a regular basis, and references the AS/NZS 2293 series as the applicable standard. That obligation sits with you regardless of whether you manage a commercial office, an industrial facility, or a construction site.
The most common audit failures:
- Inadequate viewing distance: Exit signs carry a printed maximum viewing distance on the face, either 24 metres or 40 metres depending on the sign specification. Placing a 24-metre sign at the end of a 30-metre corridor fails compliance, even if the sign lights up and occupants can see it clearly.
- Incorrect mounting height: Signs mounted below 2 metres or incorrectly positioned above 2.7 metres can fail inspection. Door head alignment matters.
- Obstructed sightlines: Shelving, signage, roller doors, and temporary partitions introduced after installation can block a previously compliant egress path. A system that passed at fit-out may not pass today if the layout has changed.
- Incomplete discharge testing: A test stopped before 90 minutes, or performed without recording the result, does not satisfy Part 2. Many facilities note that someone "conducted" a test but record neither the duration nor the outcome.
- Gaps in coverage: Fitout extensions, renovations, or subdivisions where nobody updated the emergency lighting plan to match.
The annual fire safety audit overview on the Checkpoint Group blog covers common oversights across multiple fire safety systems. Emergency lighting consistently appears on that list, and for good reason. It is the system most people assume is fine because the green light on the fitting is still on.

Maintained and Non-Maintained Fittings: Know the Difference
One distinction that matters in both specification and compliance is the difference between maintained and non-maintained emergency fittings.
A maintained fitting operates continuously as part of the normal lighting circuit. The fitting stays illuminated at all times, with the emergency module taking over if power fails. Cinemas, theatres, and any space requiring continuously visible exit routes typically use maintained fittings regardless of normal lighting conditions.
A non-maintained fitting only activates when mains power fails. These are standard in most commercial and industrial settings, where normal lighting is sufficient during operation.
The distinction affects how you test, how you document, and how you interpret what a "working" fitting means. A non-maintained fitting that looks fine during a normal inspection may still fail the 90-minute discharge test if the battery has degraded. Condition on the outside tells you nothing about battery capacity under load.
Exit Lighting in the Context of Your Broader Safety Setup
Emergency exit lighting does not operate in isolation. It is one component of a broader emergency response infrastructure that includes alarm systems, emergency warning systems, and egress planning. A lighting system that meets AS 2293 but feeds into a poorly documented evacuation plan has not solved the underlying safety problem.
When Checkpoint Group reviews a site's safety setup, our team assesses exit and emergency lighting alongside emergency warning systems, signage, and fire protection equipment. The question is not just whether the individual components comply. It is whether they work together effectively when the situation demands it.
If you are not certain your current emergency lighting setup would survive a compliance audit, the gap between "probably fine" and "definitely compliant" is not a comfortable place to sit.
Frequently Asked Questions
Is Your Emergency Lighting Audit-Ready?

Compliance with AS 2293 is not a one-time task. It is a continuous maintenance obligation with specific testing intervals, documentation requirements, and performance standards that apply for the life of the building.
If you are not confident your current system is fully compliant, or if your maintenance records have gaps, Checkpoint Group can review your emergency lighting setup and identify exactly where the risks sit. From supply through to ongoing maintenance, our team works with facility managers and safety officers across Australia to keep exit and emergency lighting performing to standard.